The Elevation 1+ DrvCAN Error Explained
07/09/2010

DrvCan or Drive CAN as the expanded message would read is the processor stating that it cannot communicate with the inverter drive via its CAN data bus. This is the primary means of communication between the two items and without it an Elevation 1+ cannot function.
| Possible Cause | Check… |
| Drive not powered up, indicated by neither the red or green LEDs on the top of the inverter being illuminated or flashing |
|
|
No terminating resistor |
There is a resistor fitted between LO and HI on the CAN module |
|
Faulty CAN module |
The pin header is correctly and fully inserted through the CAN module and into the inverter |
|
Bad cable between inverter and PCB |
|
|
Inverter incorrectly programmed |
|
|
Faulty PCB |
Swap with a working board to see if the fault moves with the board or stays with the inverter |